The C-IS-0404S module on the CIB Common Installation Bus® with 4x AI / DI and 4x DO and is built-in. It contains four binary outputs that can be used (in pairs DO1 with DO2 and DO3 with DO4) as 'H bridges' for controlled polarity reversal or as PWM outputs of the open collector type eg for control of model actuators (only with external power supply), or as common transistor outputs 24 VDC 50 mA. It contains four universal inputs configurable in pairs (DI / AI1 with DI / AI2 and DI / AI3 with DI / AI4) either as binary allowing connection of a potential-free contact against a common GND conductor or as analog for direct connection of passive resistance sensors Pt1000, Ni1000, NTC 12k , KTY 81-121 (measured resistance value is converted in the module directly to a numerical temperature value), or general resistance measurement in the range of 0–100 kΩ or DC voltage in the range of 0–2 V. The TXN 143 14 module is in a shrink tube and is equipped with terminal blocks with tongue terminals. The TXN 143 14.01 module is not protected by a tube or does not contain terminal blocks, all signals are routed to the socket strips, a built-in connection is assumed here by sliding the module onto the plugs of the expansion board.
| COM - System buses |
|---|
| CIB - Common Installation Bus (R): Installation I/O bus | 1x CIB slave |
| DI - Organization of binary inputs |
|---|
| Total number of binary inputs | 2 |
| Number of groups of binary inputs | 1 |
| Organization of binary inputs into groups | 2x DI (AI1 - AI2) |
| DI - Parameters of binary inputs DC (group A) |
|---|
| Parameters valid for inputs on the terminals | AI1 - AI2 |
| Number of inputs in group | 2 |
| Common wire | GND - module ground |
| Combined input type | DI / AI - measurement of resistance sensors, sensing of potential-free contacts and balanced loops |
| Galvanic isolation of inputs from internal/peripheral circuits | No |
| Max. measuring voltage on the connected contact | 3,3 V DC |
| Internal input resistance | 2 kΩ |
| Max. resistance for closed contact, log. 1 | < 0,5 kΩ |
| Min. resistance for open contact, log. 0 | > 4,2 kΩ |
| Balanced resistance input | 2× 1k1 (tamper/0/1/tamper) |
| DO/RO - Organization of binary outputs |
|---|
| Total number of binary outputs | 5 |
| Number of binary output groups | 2 |
| Organization of binary outputs into groups | 4x (DO1 - DO4) 1x (DO5) |
| DO - Parameters of binary transistor outputs (group A) |
|---|
| Parameters valid for the terminals | DO1-DO4 |
| Number of outputs in group | 4 |
| Organization of transistor outputs into groups | 3 (DO1-DO3) |
| Output type | MOSFET (High-side switch) |
| Galvanic separation from internal circuits | No |
| Galvanic isolation of the outputs from CIB | No |
| Diagnostics | No |
| Switching voltage | 9 - 30 V DC |
| Group current | 160 mА |
| Output current | 160 mA |
| Switching time | typ. 40 μs (12-24V, 60-160mA) |
| Opening time | typ. 70 μs (12-24V, 60-160mA) |
| Residual current | max. 10 μA |
| Short circuit protection | Yes |
| Special functions (A) | PWM |
| Operating frequency | 100 Hz ÷ 2 kHz |
| DO - Parameters of binary transistor outputs (group B) |
|---|
| Parameters valid for the terminals | DO5 |
| Common group conductor | COM2 |
| Output type | transistor output |
| Galvanic separation from internal circuits | Yes |
| Switching voltage | 0 - 48V DC |
| Switching current, output load | 80 mA (160mA @ 25˚C) |
| Residual current | 5 μA max. |
| Short circuit protection | No |
| Special functions | PWM |
| Operating frequency | 100 Hz ÷ 2 kHz |
| AI - Organization of analog inputs |
|---|
| Total number of analog inputs | 2 |
| Number of inputs per group | 2 |
| Number of analog input groups | 1 |
| Organization of analog inputs into groups | 2x (AI1, AI2) |
| Input type | AI / DI - combined |
| Common wire | GND terminal |
| Galvanic separation from internal circuits | No |
| Diagnostics | overload signaling in status word |
| Digital resolution | 10 bit |
| AI - Analog Input Ranges (Group A) |
|---|
| Parameters valid for inputs on the terminals | AI1, AI2 |
| Passive sensor | NTC Thermistor 12k / 25 °C (-40 to + 125 °C) |
| Power supply |
|---|
| Supply voltage, tolerances | 24/27 V DC from CIB bus |
| Auxiliary power supply - voltage | Supply output +22V OUT: U0 = CIB bus voltage -1 V, Iout max = 60mA, internal resistance R < 88 Ω |
| Typical power input | 0,5 W |
| Maximum power input | 2,2 W |
| Module thermal/power loss | 0,4 W |
| Power supply from CIB - typical current consumption (mA) | 20 mA |
| Power supply from CIB - maximum current consumption (mA) | 80 mA |
| Description of power supply | Difference between typical and maximum power input is given by possible load of CIB buses and number of switched outputs and CPU load |
| Thermal/power loss of the module max. | 0.65W (at maximum consumption of outputs powered by auxiliary voltage +22V OUT) |
| Size and weight |
|---|
| Weight approx. | 7 g |
| Product dimensions (width x height x depth) | 55 × 26 × 16 mm |
| Operating conditions, product standards |
|---|
| Product standard | ČSN EN 60730-1 ed.4 :2017 (EN 60730-1:2016) -Automatic electronic control device (for household and similar purposes) |
| Protection class of electrical object | III, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016) |
| IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) | IP10B |
| Operating areas | Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005) |
| Degree of pollution | 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007) |
| Overvoltage category installation | II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007) |
| Type of device | In the installation box, under the cover |
| Working position | Any |
| Type of operation (operating frequency) | Continuous |
| Ambient operating temperatures | 0 ° C to + 55 ° C |
| Operating relative humidity | from 10 % up to 95 % without condensation |
| Operating atmospheric pressure | min. 70 kPa (<3,000 m above sea level) |
| Storage temperatures | –25 ° C to + 85 ° C |
| Electromagnetic compatibility, Mechanical endurance |
|---|
| Electromagnetic compatibility / Emission | ČSN EN 55022 ed2:2007 (mod CISPR22:2005) |
| Electromagnetic compatibility / Immunity | min. according to ČSN EN 60730-1 ed.2: 2001 |
| Sinusoidal vibration endurance | 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.) |
| Packaginng, transportation, storage |
|---|
| Description | Модуль упакован в антистатический пакет. Эта документация также является частью пакета. Внешняя упаковка осуществляется в соответствии с объемом заказа и способом транспортировки в транспортной упаковке, снабженной этикетками и другими данными, необходимыми для транспортировки. Продукт не должен подвергаться воздействию прямых погодных условий во время транспортировки и хранения. Соложение продукта разрешено только в чистых помещениях.
без токопроводящей пыли, агрессивных газов и паров. Наиболее подходящая температура хранения - 20 ° C. |
| Installation |
|---|
| Assembly description | The module C-DM-0001B-SL is mounted in arbitrary positioninto instalation box under a lid or under device located in box. |
| Connection |
|---|
| Connection of power and system communication | terminal block with spring terminal 0.15-0.5 mm2, push-in |
| Connection of inputs / outputs | terminal block with spring clamp 0.15-0.5 mm2, push-in |
| Connection description | An example of module connection is shown in the following figure. |
| Module operation |
|---|
| Module configuration | The module is operated, set up and diagnosed from the Mosaic development environment. |
| Commissioning | The module is operated, set and diagnosed from the MOSAIC programming environment or other parameterization software. The module is ready for operation after connecting the supply voltage and the CIB bus. The HW address is indicated on the label on the module. |
| Module diagnostics | The basic diagnostics is performed internally and the result is available in the relevant registers of the Mosaic environment. |
| Maintenance |
|---|
| Description | The module does not require any maintenance under general installation conditions. The operations in which a part of the module has to be dismantled must always be carried out with the supply voltage disconnected. |
| Notice | Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!! |
| Warranty |
|---|
| Generally | Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s. |
| Notice | You must meet all the conditions of this documentation before turning on the system.
The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it.
Documentation subject to change. |