C-IF-6400R is a matrix of 8 x 8 temperature sensors (64 pixels) on the CIB bus - Common Instalation Bus®. Sensor Grid-EYE is based on MEMS technology. Each pixel, independently of the others, transmits the temperature value directly in engineering units. The range of measured temperatures is from 0 to 80 ° C. Thanks to the silicon lens, it is possible to actively monitor the angle of 60 °. Fast measurement and transfer (1x or 10x per second) of all values to the basic Foxtrot module allows to prepare programs for static and dynamic decision and recognition functions above this field, it is possible to detect the presence, movement, speed and direction of moving objects
| COM - System buses |
|---|
| CIB - Common Installation Bus (R): Installation I/O bus | 1x CIB slave |
| Parameter des Temperatursensors |
|---|
| Temperature - Sensor type | SI 7020 |
| Temperature - Measurement range | 0°C ÷ 50°C |
| Temperature - Resolution | 0,1 °C |
| Temperature - Measurement accuracy | typ. ±0,4 °C |
| Humidity sensor parameters |
|---|
| Relative humidity - Sensor type | SI 7020 |
| Relative humidity - Measurement range | 0 ÷ 100 %RH |
| Relative humidity - Resolution | 1 % RH |
| Power supply |
|---|
| Supply voltage, tolerances | 24/27 V DC from CIB bus |
| Maximum power input | 0,15 W |
| Power supply from CIB - maximum current consumption (mA) | 10 mA |
| Power supply from CIB - Galvanic separation of power supply from internal circuits | No |
| Power supply from CIB - internal protection | No |
| Size and weight |
|---|
| Weight approx. | 125 g |
| Product dimensions (width x height x depth) | 109 × 99 × 19,8 mm |
| Operating conditions, product standards |
|---|
| Product standard | ČSN EN 60730-1 ed. 3:2012 (mod IEC 60730-1:2010) |
| Protection class of electrical object | III, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016) |
| IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) | IP10B |
| Operating areas | Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005) |
| Degree of pollution | 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007) |
| Overvoltage category installation | II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007) |
| Type of device | On the wall |
| Working position | Vertical |
| Type of operation (operating frequency) | Continuous |
| Ambient operating temperatures | 0 °C to + 55 °C |
| Operating temperature minimum (° C) | 0°C |
| Operating relative humidity | from 10 % up to 95 % without condensation |
| Operating atmospheric pressure | min. 70 kPa (<3,000 m above sea level) |
| Storage temperatures | –25 °C to +70 °C |
| Electromagnetic compatibility, Mechanical endurance |
|---|
| Electromagnetic compatibility / Emission | ČSN EN 55022 ed2:2007 (mod CISPR22:2005) |
| Electromagnetic compatibility / Immunity | min. according to ČSN EN 60730-1 ed.2: 2001 |
| Sinusoidal vibration endurance | 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.) |
| Packaginng, transportation, storage |
|---|
| Description | The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C |
| Installation |
|---|
| Assembly description | The module is mounted in a vertical position on a standard installation box with a spacing of fixing screws of 60 mm or directly on the wall. Mounting holes are pre-molded in the bottom of the C-RC-0011R. The lower part should be screwed to the wall in a position where the inscription "LOWER" is legible. The lower part and the upper part (with display) are snapped in by latches, by slightly pressing the sides of the box and by light pulling both parts can be separated from each other. |
| Connection |
|---|
| Connection of power and system communication | terminal block with screw terminal 1.5 mm2 |
| Module connection | The module is implemented as a CIB bus module, which provides communication and power supply to the module. The CIB bus can have any topology and branching up to a distance of 500 m and up to 32 units on one CIB branch. The CIB bus master is the FOXTROT basic unit with an internal module or the external module CF-1141 with FW version 1.8 and higher. For more information, see the manual Peripheral modules on the CIB bus TXV 004 13. |
| Module operation |
|---|
| Module configuration | The module is operated, set up and diagnosed from the Mosaic development environment. |
| Module diagnostics | The basic diagnostics is performed internally and the result is available in the relevant registers of the Mosaic environment. |
| Maintenance |
|---|
| Description | The module does not require any maintenance under general installation conditions. |
| Notice | Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!! |
| Warranty |
|---|
| Generally | Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s. |
| Notice | You must meet all the conditions of this documentation before turning on the system.
The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it.
Documentation subject to change. |