The C-DM-0002L-10V module is designed for independent two-channel control of electronic LED ballasts or fluorescent lamps, controlled by 0-10 V DC or 1-10 V DC. To completely disconnect the ballasts from the main power supply, the module contains 2 relay outputs, one with an NC contact and the other with changeover contacts. Of course, analog inputs and relay outputs can also be used universally for other purposes. The module is designed for a DIN rail switchboard, but it can also be built into the body of the luminaire. It is connected to the Foxtrot basic module via a two-wire CIB Common Installation Bus®.
| COM - System buses |
|---|
| CIB - Common Installation Bus (R): Installation I/O bus | 1x CIB slave |
| AO - Analog output parameters |
|---|
| Number of analog outputs | 6 |
| The number of groups of analogue outputs | 2 |
| Number of outputs in group | 3 |
| Number of outputs and their organization into groups | Each of terminals B1, B5, B9 (LED+) has a maximum current of 10A, but the sum of currents through these terminals must not exceed 24A.
A maximum of 4A current may flow through each of terminals B2, B3, B4, B6, B7, B8, (LED1 - 6)but the total sum of these currents through terminals B2, B3, B4, B6, B7, B8 must not exceed 24A.
The operating voltage is 12 - 48V DC, while the value of 48V DC applies from serial number 1226 (April 2017), up to this serial number is the maximum value of 24V DC. |
| Common wire of group | plus |
| Galvanic isolation from internal circuits | No |
| Output type | active voltage output in switching mode |
| External power supply | max 48V DC (up to serial number 1226 only 24V DC) |
| Power supply |
|---|
| Supply voltage, tolerances | 24/27 V DC from CIB bus |
| Auxiliary power supply - voltage | The supply voltage for the LEDs must be selected with regard to the LED light sources used.
The outputs for LED strips have a common positive supply pole (anode) marked as LED +.
For LED + outputs it is necessary to observe the maximum current of one terminal 10 A,
The supply voltage is usually from 12 V DC and up to a maximum of 48 V DC.
The 48V DC power supply is valid from serial number 1226 (April 2017), up to this serial no. only 24V DC! |
| Typical power input | 3 W |
| Maximum power input | 5 W |
| Module thermal/power loss | 5 W |
| Maximum current consumption (mA) | < 20 mA |
| Galvanic separation of power supply from internal circuits | No |
| Internal protection | Yes, PTC reversible fuse |
| Size and weight |
|---|
| Weight approx. | 100 g |
| Product dimensions (width x height x depth) | 52 x 90 x 58 mm |
| Module width in multiples of M (17.5 mm) | 3M |
| Module width | 52 mm |
| Module height | 90 mm |
| Module depth | 58 mm |
| Operating conditions, product standards |
|---|
| Product standard | ČSN EN 60730-1 ed.4 :2017 (EN 60730-1:2016) -Automatic electronic control device (for household and similar purposes) |
| Protection class of electrical object | III, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016) |
| IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) | IP20 |
| Operating areas | Normal, according to ČSN 33 2000-3: 1995 (mod IEC 364-3: 1993) |
| Degree of pollution | 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007) |
| Overvoltage category installation | III, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007) |
| Type of device | Module on DIN rail |
| Working position | Vertical |
| Type of operation (operating frequency) | Continuous |
| Ambient operating temperatures | 0 °C to +40 °C |
| Operating temperature minimum (° C) | 0°C |
| Operating relative humidity | from 10 % up to 95 % without condensation |
| Operating atmospheric pressure | min. 70 kPa (<3,000 m above sea level) |
| Storage temperatures | –25 °C to +70 °C |
| Electromagnetic compatibility, Mechanical endurance |
|---|
| Electromagnetic compatibility / Emission | A, according to EN 55032 ed. 2: 2017 (idt CISPR 32: 2015) |
| Emmisions - note | In premises where the use of radio and television receivers can be expected to be used a distance of 10 m from these devices may cause radio interference. In such a case, the user may be required to take appropriate action. |
| Electromagnetic compatibility / Immunity | min. as required by EN 61131-2: 2007 |
| Sinusoidal vibration endurance | 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.) |
| Packaginng, transportation, storage |
|---|
| Description | The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C |
| Installation |
|---|
| Assembly description | Switchboard mounting |
| Attention! | The device may contain parts with dangerous voltages, covers being removed, or cabling manipulated, or disconnect the appropriate circuits or turn off the power !. |
| Connection |
|---|
| Connection of power and system communication | connector with 2.5 mm2 screw terminal |
| Connection of inputs / outputs | connector with screw terminal 2.5 mm2 |
| Module installation tools | (-) 3 mm, flat screwdriver |
| Module operation |
|---|
| Module configuration | The module is operated, set up and diagnosed from the Mosaic development environment. |
| Module diagnostics | The basic diagnostic system of the module is a part of its standard software. It operates from module power on and operates independently of the user. Diagnostic error states of the module and connected peripheral modules of the assembly are signaled |
| Maintenance |
|---|
| Description | The module does not require any maintenance under general installation conditions. The operations in which a part of the module has to be dismantled must always be carried out with the supply voltage disconnected. |
| Notice | Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!! |
| Warranty |
|---|
| Generally | Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s. |
| Notice | You must meet all the conditions of this documentation before turning on the system.
The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it.
Documentation subject to change. |