C-IS-0504M is a module on the CIB bus with a total of 9 inputs / outputs in combination 3x combined AI / DI input for sensing contacts and measuring resistance thermometers, 2x analog input specialized for measuring AC resistances (excluding long-term electrolysis in a humid environment - icing, precipitation, level probes) 1x semiconductor output with pulse width modulation (PWM from 100 Hz to 2 kHz and load capacity max. 4W) 2x relay output 5 A, 1x relay output 16A, with resistance to inrush current up to 80 A The individual relay outputs have a status LED indication and can be manually controlled locally by buttons on the module panel. Use Inputs and outputs can be used as general AI / DI and RO Specialized use: Controlled heating supply and measurement of precipitation detector S-RS-01I, Heating supply and measurement of icing sensors with a nominal voltage of 24 V. Up to 2 probes for level measurement, eg for limit monitoring of water in the tank.
| RO - Parameters of binary relay outputs (group A) |
|---|
| Number of relay outputs | 8 |
| Number of output groups | 3 |
| Number of outputs in group | 1 |
| Organization of relay outputs into groups | Independently |
| Output type | electromechanical relay, unprotected output |
| Contact type | NO / NC changeover contact |
| Diagnose | Alarm signaling on panel module |
| Switching current | 16 A max. NO/10 A max NC, 100 mA min. |
| Switching voltage | 300 V max., 5 V min. |
| Short-term output overload - inrush | 80 A max. (20 ms max.) |
| Contact closing time | typ. 15 ms |
| Contact opening time | typ. 5ms |
| Mechanical life | min. 5,000,000 cycles |
| Short-circuit protection | No |
| Treatment of inductive load | External RC element, varistor (AC), diode (DC) |
| Insulation voltage between outputs and internal circuits | 3750 V AC |
| Notice! | An insulation voltage of 3750V AC is not guaranteed between the contacts on the common terminal block |
| Power supply |
|---|
| Power supply from CIB - voltage | 24/27 V DC |
| Auxiliary power supply - voltage | 24 V DC, +- 10% |
| Typical power input | 4 W |
| Maximum power input | 4,5 W |
| Module thermal/power loss | 4 W |
| Maximum current consumption (mA) | 200 mA |
| Power supply from CIB - maximum current consumption (mA) | 160 mA |
| Galvanic separation of power supply from internal circuits | No |
| Size and weight |
|---|
| Weight approx. | 350 g |
| Product dimensions (width x height x depth) | 105 x 92 x 58 mm |
| Module width in multiples of M (17.5 mm) | 6M |
| Module width | 105 mm |
| Module height | 92 mm |
| Module depth | 58 mm |
| Operating conditions, product standards |
|---|
| Product standard | ČSN EN 61131-2 ed.2: 2008 (IEC 61131-2: 2007) и ČSN EN 60730-1 ed.4: 2017 (EN 60730-1: 2016) |
| Protection class of electrical object | I, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016) |
| IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) | IP20 |
| Operating areas | Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005) |
| Degree of pollution | 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007) |
| Overvoltage category installation | II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007) |
| Type of device | Module on DIN rail |
| Working position | Vertical |
| Type of operation (operating frequency) | Continuous |
| Ambient operating temperatures | -10 °C to + 55 °C |
| Operating temperature maximum (° C) | +55°C |
| Operating temperature minimum (° C) | -10°C |
| Operating relative humidity | from 10 % up to 95 % without condensation |
| Operating atmospheric pressure | min. 70 kPa (<3,000 m above sea level) |
| Storage temperatures | –25 °C to +70 °C |
| Electromagnetic compatibility, Mechanical endurance |
|---|
| Electromagnetic compatibility / Emission | B, according to EN 55022: 1999 (mod CISPR22: 1997) |
| Emmisions - note | In premises where the use of radio and television receivers can be expected to be used a distance of 10 m from these devices may cause radio interference. In such a case, the user may be required to take appropriate action. |
| Electromagnetic compatibility / Immunity | min. according to ČSN EN 60730-1 ed.2: 2001 |
| Sinusoidal vibration endurance | 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.) |
| Packaginng, transportation, storage |
|---|
| Description | The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C |
| Installation |
|---|
| Attention! | The device may contain parts with dangerous voltages, covers being removed, or cabling manipulated, or disconnect the appropriate circuits or turn off the power !. |
| Connection |
|---|
| Connection of power and system communication | connector with 2.5 mm2 screw terminal |
| Connection of inputs / outputs | connector with screw terminal 2.5 mm2 |
| Module operation |
|---|
| Module configuration | LEDs on the front of the module are used to diagnose the condition. To set the button on the module as described in the diagrams section |
| Maintenance |
|---|
| Description | The module does not require any maintenance under general installation conditions. |
| Notice | Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!! |
| Warranty |
|---|
| Generally | Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s. |
| Notice | You must meet all the conditions of this documentation before turning on the system.
The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it.
Documentation subject to change. |