| Technical data |
KL2012 |
| Connection technology |
4-wire |
| Number of outputs |
2 |
| Nominal voltage |
24 V DC (-15%/+20%) |
| Load type |
ohmic, inductive, lamp load |
| Max. output current |
0.5 A (short-circuit proof) per channel |
| Short-circuit current |
< 2 A |
| Breaking energy |
< 150 mJ/channel |
| Reverse voltage protection |
– |
| Electrical isolation |
500 V (K-bus/field potential) |
| Current consumption power contacts |
typ. 15 mA + load |
| Current consumption K-bus |
typ. 5 mA |
| Bit width in the process image |
2 outputs |
| Configuration |
no address or configuration setting |
| Weight |
approx. 55 g |
| Operating temperature |
0…55°C |
| Storage temperature |
-25…+85°C |
| Relative humidity |
95%, no condensation |