| General specifications |
| Signal type |
Digital Input |
| Functional safety related parameters |
| Safety Integrity Level (SIL) |
SIL 2 |
| Supply |
| Connection |
terminals 14, 15 |
| Rated voltage |
103.5 ... 126 V AC , 45 ... 65 Hz |
| Power dissipation |
1.2 W |
| Power consumption |
max. 1.3 W |
| Input |
| Connection side |
field side |
| Connection |
terminals 1+, 2+, 3-; 4+, 5+, 6- |
| Rated values |
acc. to EN 60947-5-6 (NAMUR) |
| Open circuit voltage/short-circuit current |
approx. 8 V DC / approx. 8 mA |
| Switching point/switching hysteresis |
1.2 ... 2.1 mA / approx. 0.2 mA |
| Line fault detection |
breakage I ≤ 0.1 mA , short-circuit I > 6 mA |
| Pulse/Pause ratio |
min. 20 ms / min. 20 ms |
| Output |
| Connection side |
control side |
| Connection |
output I: terminals 7, 8, 9 ; output II: terminals 10, 11, 12 |
| Output I, II |
signal ; relay |
| Contact loading |
253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load |
| Energized/De-energized delay |
approx. 20 ms / approx. 20 ms |
| Mechanical life |
107 switching cycles |
| Transfer characteristics |
| Switching frequency |
≤ 10 Hz |
| Galvanic isolation |
| Input/Output |
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Input/power supply |
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Output/power supply |
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Output/Output |
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Indicators/settings |
| Display elements |
LEDs |
| Control elements |
DIP switch |
| Configuration |
via DIP switches |
| Labeling |
space for labeling at the front |